INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.
SAFETY
INSTRUCTIONS
This safety alert symbol will be used in this manual and on the
Technologic 5500 Safety Instruction decal to draw attention to
safety related instructions. When used, the safety alert symbol
means ATTENTION! BECOME ALERT! YOUR SAFETY IS
INVOLVED! FAILURE TO FOLLOW THE INSTRUCTION
MAY RESULT IN A SAFETY HAZARD!
Technologic
5500 Series
Variable Primary Pump and
Valve Controller
WARNING LABEL PART #S11550
INSTALLED IN THIS LOCATION.
IF MISSING IT MUST BE REPLACED.
DESCRIPTION
Microprocessor based dedicated pump controller for variable
volume pumping systems. The control panel consists of the
following components: microprocessor, operator interface
with 4 line display and membrane key pad, and 24 VDC
power supply. Multi-pinned connecting cables for connection
to bypass panels are available as options.
OPERATIONAL LIMITS
See the control panel nameplate for operating voltage, current
draw, as well as information on the equipment to be con-
nected to the control panel.
VARIABLE SPEED PUMPING SYSTEMS
INSTRUCTION MANUAL
INSTRUCTION MANUAL
S14334B
Zobrazit stránku 0
1 2 3 4 5 6 ... 53 54

Shrnutí obsahu

Strany 1 - Valve Controller

INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.SAFETYINSTRUCTIONSThis safety alert symbol will be used in this manual and on theTechnologic 5

Strany 2

102.2.2 GroutAfter the frame has been leveled and securely boltedto the pad, a good grade of grout should be installedbeneath the base. A suggested m

Strany 3

113.1 Power-upPut LOCAL-REMOTE-OFF (LRO) switch in theLOCAL position. Put the optional AUTO-OFF-HANDswitch in the AUTO position. Turn main disconnect

Strany 4 - INDEX (continued)

From the Technologic Pump Controller screen,shown in section 3.2, press the SETUP/3 key to getto the Setup Selection Menu shown below. Setup Selectio

Strany 5

13Typically the variable value is zero at 4mA for manysensors. An exception would be for a temperaturesensor. Enter the desired zero value by pressi

Strany 6 - Glossary of Terms

144.1.12Sensor Setup Exit (not PV)If NO/0 was selected in section 4.1.8 (the sensordoes not provide a PV), the display will show: Sensor No ## (

Strany 7 - Section 1 - General

Table 4: Pump Off Delay Variables15State DescriptionN/A pump not available as defined by setupRdy pump available, not runningOn pump is runningOff pum

Strany 8

164.2.9 Low Load TransferFrom section 4.2, press 4 and ENTER to get to theLow Load Transfer screen shown below. Low Load TransferPoint ### % SpeedEna

Strany 9

17Press NO/0 and ENTER to edit the fields. To returnto the Stage/Destage Menu, shown in section 4.3.1,press YES/7 and ENTER. See Table 8 below for a

Strany 10

18Variable Unit Description Default Value Range Field ValueAFD Fail s Proof timer prior to setting the AFD fail alarm 20 0-999Pr TmPump Fail s Proof

Strany 11

194.3.5 Bypass SetupFrom the System Setup Menu, shown in section 4.3,press F1/LOG/5 and ENTER to get to the BypassSetup screen shown below. No of AFD

Strany 12

2PrefaceThe following manual describes the new microproces-sor based Technologic 5500 Variable Primary PumpController. This unit is in the tradition

Strany 13

204.3.8 Password SetupFrom the System Setup Menu, shown in section 4.3,press F3/INFO/8 and ENTER to get to the PasswordSetup screen shown below. En

Strany 14

214.3.9.2 DOFrom the I/O Setup Menu, shown in section 4.3.9,press SET POINT/2 and ENTER to get to the DOscreen shown below. Total Avail. DO: #Opt. DO

Strany 15

224.3.10 Communication Setup MenuFrom the System Setup Menu, shown in section 4.3,press 10 and ENTER to get to the CommunicationSetup Menu shown below

Strany 16

234.3.10.4 BACnet/IPFrom the Communication Setup Menu, shown in sec-tion 4.3.10, press ALTERNATION/4 and ENTER to getto the BACnet/IP screen shown bel

Strany 17

244.3.14 Load from FlashFrom the System Setup Menu, shown in section 4.3,press 13 and ENTER to get to the Save to Flashscreen shown below. **WARNING*

Strany 18

254.4.7 Disp TestFrom the Test Selection Menu, shown in section 4.4,press YES/7 and ENTER to get to the Disp Test Screenshown below. Press Clear to

Strany 19

26Press the numeric key for the chiller you wish tosetup. The chiller number is limited to the maximumnumber of chillers. Press ENTER to proceed with

Strany 20

274.7 Bypass Valve SetupFrom the Setup Selection Menu, shown in section 4,press YES/7 and ENTER to get to the Bypass ValveSetup Menu shown below. S

Strany 21

28Section 5 - Operation5.1 Status Screens5.1.1 Technologic Pump Controller ScreenThe Technologic Pump Controller screen displays thedate, time, stat

Strany 22

295.1.9 Active Values Seq ScreenPressing NEXT SCREEN, the controller will displaythe Active Values Seq screen shown below.Active ValuesSeq:

Strany 23

3SECTION 1 - GENERAL Page 1.1 Purpose of Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Strany 24

30Press the SETUP/3 key followed by ENTER to pro-ceed to manual bypass operation. The display willnow show the following:Technologic Pump ControllerD

Strany 25

315.9AlternationFrom the Technologic Pump Controller screen, shownin section 3.2, press Alternation/4 to get to the Alter-nation screen shown below.

Strany 26

32The following is a description of the hardware, diag-nostics, and corrective action to maintain a processbeing controlled by the Technologic 5500 Va

Strany 27

336.10 Field RepairGeneral - typical field repair should include: replac-ing fuses, replacing input/output modules and assur-ing connections are corr

Strany 28 - Section 5 - Operation

346.13.3 Data Log MenuFrom the Logging Menu, shown in section 6.13, pressSETUP/3 and ENTER to get to the Data Log Menushown below. Selection : #

Strany 29

356.13.4.4 System Reset LogFrom the Operation Log Menu, shown in section6.13.4, press ALTERNATION/4 and ENTER to get tothe System Reset Log screen sho

Strany 30

36SYSTEM PIPING AND UNITINSTALLATION – FINAL CHECK LIST____ 1. Is the unit base properly level, grouted and secured?____ 2. Are all lubrication points

Strany 31

Appendix C - Valid I/O CodesCode Function Description I/O Type Range Equate to the Signal101 Pump 1 Status (On/Off) DO 1/0 On/Off102 Pump 2 Status (On

Strany 32 - Section 6 - Maintenance

38Appendix D - BACnet MS/TP Protocol Implementation Conformance StatementBACnet MS/TP Protocol Implementation Conformance StatementDate: 9/13/06Vendor

Strany 33

39Appendix E - BACnet IP Protocol Implementation Conformance StatementBACnet IP Protocol Implementation Conformance StatementDate: 9/13/06Vendor Name:

Strany 34

4INDEX (continued)4.2.2 Number of Pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Strany 35

40Appendix F - BACnet Communications ObjectsObject Identifier Object Name Object Type Present Value/RangeBinary Input, 1 P1 Overload Failure BINARY_IN

Strany 36 - Appendix B

41Appendix F (cont'd.)Object Identifier Object Name Object Type Present Value/RangeBinary Input, 59 AI #9 Failure BINARY_INPUT 1 = Failure

Strany 37 - Appendix C - Valid I/O Codes

42Appendix F (cont'd.)Object Identifier Object Name Object Type Present Value/RangeAnalog Value, 34 Setpoint #6 ANALOG_VALUE 0 to Span (in Techno

Strany 38

43Appendix G - LonWorks Communications PointsSNVTNV LengthIndex Name SNVT Type (bytes) POINT DESCRIPTION RANGE/VALUE Unit0 nvoPmp1_OL_Fail SNVT_switc

Strany 39

44Appendix G (cont'd.)SNVTNV LengthIndex Name SNVT Type (bytes) POINT DESCRIPTION RANGE/VALUE Unit47 nvoPmp5_On_Off SNVT_switch(95) 2 Pump #5 On

Strany 40

45Appendix G (cont'd.)SNVTNV LengthIndex Name SNVT Type (bytes) POINT DESCRIPTION RANGE/VALUE Unit94 nvo_KW1 SNVT_power_kilo (15) 2 KW #1 0 to S

Strany 41 - Appendix F (cont'd.)

46Appendix G (cont'd.)SNVTNV LengthIndex Name SNVT Type (bytes) POINT DESCRIPTION RANGE/VALUE Unit141 nviSeq_Alt SNVT_switch(95) 2 Pump Sequence

Strany 42

47Appendix H - Metasys N2 Communications PointsNPT NPA POINT DESCRIPTION RANGE/VALUE UNITBI 1 Pump #1 Overload Failure 1 = Failure 0 = O.K.BI 2 Pump

Strany 43

48Appendix H (cont'd.)NPT NPA POINT DESCRIPTION RANGE/VALUE UNITBI 50 System Start/Stop 1 = Start 0 = StopBI 51 Analog Input #1 Fai

Strany 44 - Appendix G (cont'd.)

49Appendix H (cont'd.)NPT NPA POINT DESCRIPTION RANGE/VALUE UNITADI 19 System KW 0 to Span (in Technologic User Setup Menu) KWADI 20 Pump #1 Pow

Strany 45

5INDEX (continued)5.2 Bypass Valve Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Strany 46

50Appendix I - Modbus RTU Communications PointsFunction ModbusCode Point # Point Description Range/Value Address Unit02 1 Pump #1 Overload Failure 1 =

Strany 47

51Appendix I (cont'd.)Function ModbusCode Point # Point Description Range/Value Address Unit02 51 Analog Input #1 Failure 1 = Failure 0

Strany 48 - Appendix H (cont'd.)

52Appendix I (cont'd.)Function ModbusCode Point # Point Description Range/Value Address Unit04 19 System KW 0 to Span (in Technologic User Setup

Strany 49

53Appendix J – DrawingsDrawing # Description1 Technologic 5500 Variable Primary Pump Controller – Door2 Technologic 5500 Variable Primary Pump Control

Strany 50

4 LINE DISPLAYNUMERIC KEY PADFUNCTION KEYS WITH LEDSTechnologic 5500 Operator Interface and CPUDRAWING 3.0Xylem Inc. 10661 Newkirk Street Dallas, TX 7

Strany 51 - Appendix I (cont'd.)

6NOTE: The information contained in this manual is intended to assist operating personnel by providing information on the char-acteristics of the purc

Strany 52

71.1Purpose of ManualThis manual is furnished to acquaint you with someof the practical ways to install, operate, and maintainthis unit. Read it caref

Strany 53 - Appendix J – Drawings

81.7 Ground ConnectionsA grounding terminal is provided for a dedicatedground wire connection. All provisions of theNational Electrical Code and loca

Strany 54 - Xylem Inc

91.12.4 Analog Inputs with External PowerThe following steps describe the general procedurefor rewiring an analog input sensor when the sensor'sp