50
Appendix I - Modbus RTU Communications Points
Function Modbus
Code Point # Point Description Range/Value Address Unit
02 1 Pump #1 Overload Failure 1 = Failure 0 = O.K. 10001
02 2 Pump #1 Failure 1 = Failure 0 = O.K. 10001
02 3 Pump #1 AFD Failure 1 = Failure 0 = O.K. 10003
02 4 Pump #1 Off Alarm 1 = Alarm 0 = O.K. 10004
02 5 Pump #2 Overload Failure 1 = Failure 0 = O.K. 10005
02 6 Pump #2 Failure 1 = Failure 0 = O.K. 10006
02 7 Pump #2 AFD Failure 1 = Failure 0 = O.K. 10007
02 8 Pump #2 Off Alarm 1 = Alarm 0 = O.K. 10008
02 9 Pump #3 Overload Failure 1 = Failure 0 = O.K. 10009
02 10 Pump #3 Failure 1 = Failure 0 = O.K. 10010
02 11 Pump #3 AFD Failure 1 = Failure 0 = O.K. 10011
02 12 Pump #3 Off Alarm 1 = Alarm 0 = O.K. 10012
02 13 Pump #4 Overload Failure 1 = Failure 0 = O.K. 10013
02 14 Pump #4 Failure 1 = Failure 0 = O.K. 10014
02 15 Pump #4 AFD Failure 1 = Failure 0 = O.K. 10015
02 16 Pump #4 Off Alarm 1 = Alarm 0 = O.K. 10016
02 17 Pump #5 Overload Failure 1 = Failure 0 = O.K. 10017
02 18 Pump #5 Failure 1 = Failure 0 = O.K. 10018
02 19 Pump #5 AFD Failure 1 = Failure 0 = O.K. 10019
02 20 Pump #5 Off Alarm 1 = Alarm 0 = O.K. 10020
02 21 Pump #6 Overload Failure 1 = Failure 0 = O.K. 10021
02 22 Pump #6 Failure 1 = Failure 0 = O.K. 10022
02 23 Pump #6 AFD Failure 1 = Failure 0 = O.K. 10023
02 24 Pump #6 Off Alarm 1 = Alarm 0 = O.K. 10024
02 25 System Reset Required 1 = Yes 0 = No 10025
02 26 Pump #1 Enabled 1 = Enabled 0 = Disabled 10026
02 27 Pump #1 Running In Variable Speed Mode 1 = In VSM 0 = Not In VSM 10027
02 28 Pump #1 Running In Bypass Mode 1 = In Bypass 0 = Not In Bypass 10028
02 29 Pump #2 Enabled 1 = Enabled 0 = Disabled 10029
02 30 Pump #2 Running In Variable Speed Mode 1 = In VSM 0 = Not In VSM 10030
02 31 Pump #2 Running In Bypass Mode 1 = In Bypass 0 = Not In Bypass 10031
02 32 Pump #3 Enabled 1 = Enabled 0 = Disabled 10032
02 33 Pump #3 Running In Variable Speed Mode 1 = In VSM 0 = Not In VSM 10033
02 34 Pump #3 Running In Bypass Mode 1 = In Bypass 0 = Not In Bypass 10034
02 35 Pump #4 Enabled 1 = Enabled 0 = Disabled 10035
02 36 Pump #4 Running In Variable Speed Mode 1 = In VSM 0 = Not In VSM 10036
02 37 Pump #4 Running In Bypass Mode 1 = In Bypass 0 = Not In Bypass 10037
02 38 Pump #5 Enabled 1 = Enabled 0 = Disabled 10038
02 39 Pump #5 Running In Variable Speed Mode 1 = In VSM 0 = Not In VSM 10039
02 40 Pump #5 Running In Bypass Mode 1 = In Bypass 0 = Not In Bypass 10040
02 41 Pump #6 Enabled 1 = Enabled 0 = Disabled 10041
02 42 Pump #6 Running In Variable Speed Mode 1 = In VSM 0 = Not In VSM 10042
02 43 Pump #6 Running In Bypass Mode 1 = In Bypass 0 = Not In Bypass 10043
02 44 Pump #1 On/Off 1 = On 0 = Off 10044
02 45 Pump #2 On/Off 1 = On 0 = Off 10045
02 46 Pump #3 On/Off 1 = On 0 = Off 10046
02 47 Pump #4 On/Off 1 = On 0 = Off 10047
02 48 Pump #5 On/Off 1 = On 0 = Off 10048
02 49 Pump #6 On/Off 1 = On 0 = Off 10049
02 50 System Start/Stop 1 = Start 0 = Stop 10050