47
Appendix H - Metasys N2 Communications Points
NPT NPA POINT DESCRIPTION RANGE/VALUE UNIT
BI 1 Pump #1 Overload Failure 1 = Failure 0 = O.K.
BI 2 Pump #1 Failure 1 = Failure 0 = O.K.
BI 3 Pump #1 AFD Failure 1 = Failure 0 = O.K.
BI 4 Pump #1 Off Alarm 1 = Alarm 0 = O.K.
BI 5 Pump #2 Overload Failure 1 = Failure 0 = O.K.
BI 6 Pump #2 Failure 1 = Failure 0 = O.K.
BI 7 Pump #2 AFD Failure 1 = Failure 0 = O.K.
BI 8 Pump #2 Off Alarm 1 = Alarm 0 = O.K.
BI 9 Pump #3 Overload Failure 1 = Failure 0 = O.K.
BI 10 Pump #3 Failure 1 = Failure 0 = O.K.
BI 11 Pump #3 AFD Failure 1 = Failure 0 = O.K.
BI 12 Pump #3 Off Alarm 1 = Alarm 0 = O.K.
BI 13 Pump #4 Overload Failure 1 = Failure 0 = O.K.
BI 14 Pump #4 Failure 1 = Failure 0 = O.K.
BI 15 Pump #4 AFD Failure 1 = Failure 0 = O.K.
BI 16 Pump #4 Off Alarm 1 = Alarm 0 = O.K.
BI 17 Pump #5 Overload Failure 1 = Failure 0 = O.K.
BI 18 Pump #5 Failure 1 = Failure 0 = O.K.
BI 19 Pump #5 AFD Failure 1 = Failure 0 = O.K.
BI 20 Pump #5 Off Alarm 1 = Alarm 0 = O.K.
BI 21 Pump #6 Overload Failure 1 = Failure 0 = O.K.
BI 22 Pump #6 Failure 1 = Failure 0 = O.K.
BI 23 Pump #6 AFD Failure 1 = Failure 0 = O.K.
BI 24 Pump #6 Off Alarm 1 = Alarm 0 = O.K.
BI 25 System Reset Required 1 = Yes 0 = No
BI 26 Pump #1 Enabled 1 = Enabled 0 = Disabled
BI 27 Pump #1 Running In Variable Speed Mode 1 = In VSM 0 = Not In VSM
BI 28 Pump #1 Running In Bypass Mode 1 = In Bypass 0 = Not In Bypass
BI 29 Pump #2 Enabled 1 = Enabled 0 = Disabled
BI 30 Pump #2 Running In Variable Speed Mode 1 = In VSM 0 = Not In VSM
BI 31 Pump #2 Running In Bypass Mode 1 = In Bypass 0 = Not In Bypass
BI 32 Pump #3 Enabled 1 = Enabled 0 = Disabled
BI 33 Pump #3 Running In Variable Speed Mode 1 = In VSM 0 = Not In VSM
BI 34 Pump #3 Running In Bypass Mode 1 = In Bypass 0 = Not In Bypass
BI 35 Pump #4 Enabled 1 = Enabled 0 = Disabled
BI 36 Pump #4 Running In Variable Speed Mode 1 = In VSM 0 = Not In VSM
BI 37 Pump #4 Running In Bypass Mode 1 = In Bypass 0 = Not In Bypass
BI 38 Pump #5 Enabled 1 = Enabled 0 = Disabled
BI 39 Pump #5 Running In Variable Speed Mode 1 = In VSM 0 = Not In VSM
BI 40 Pump #5 Running In Bypass Mode 1 = In Bypass 0 = Not In Bypass
BI 41 Pump #6 Enabled 1 = Enabled 0 = Disabled
BI 42 Pump #6 Running In Variable Speed Mode 1 = In VSM 0 = Not In VSM
BI 43 Pump #6 Running In Bypass Mode 1 = In Bypass 0 = Not In Bypass
BI 44 Pump #1 On/Off 1 = On 0 = Off
BI 45 Pump #2 On/Off 1 = On 0 = Off
BI 46 Pump #3 On/Off 1 = On 0 = Off
BI 47 Pump #4 On/Off 1 = On 0 = Off
BI 48 Pump #5 On/Off 1 = On 0 = Off
BI 49 Pump #6 On/Off 1 = On 0 = Off